TCQY Series Medium and High Voltage Switchgear Magnetron Soft Starter Integrated Cabinet
Classification:
1. Basic Principle
The TCQY Series Medium and High Voltage Switchgear Magnetron Soft Starter Integrated Cabinet is mainly used for the control and protection of starting and stopping squirrel-cage asynchronous motors and synchronous motors. It utilizes a new generation of autotransformer excitation soft start patent technology to successfully develop a new type of solid-state soft starting device, suitable for starting large, medium-sized, and particularly large squirrel-cage or synchronous motors.
By inserting a self-excited controllable reactor with a smoothly variable impedance into the stator circuit of the squirrel-cage or synchronous motor, the closed-loop control system automatically adjusts the size of the DC current in the self-excited controlled winding (without the need for an external high-current power source). The impedance of the self-coupling excited controllable reactor automatically decreases steplessly from high to low within a predetermined time, gradually increasing the motor terminal voltage to full voltage, thereby achieving a soft start for the motor.
2. Performance Features
◆ Different starting current curves such as constant current, ramp-up, and jump-start can be selected according to the requirements of different working conditions.
◆ Use internationally leading computer simulation technology, making the entire starting process predictable, controllable, and adjustable.
◆ User-friendly interface, convenient for setting, adjusting, and querying starting parameters.
◆ High safety and stability, long service life.
◆ Good reusability, starting performance unaffected by ambient temperature.
◆ High degree of automation, easy operation, capable of soft stopping.
3. Model Description

4. Performance Parameter Table
| Item | Parameter |
| Applicable motor voltage | 3kV-10kV (special design for 11kV motors is required) |
| Applicable motor power | 200kW~3000kW |
| Starting current | 2.5-3.5 times the rated current |
| Starting voltage drop | Less than 3V with bypass contactor |
| Starting time | 5~120s |
| Starting frequency | 1-3 times/hour |
| Starting methods | Constant current, ramp, and jump start current curves |
| Stopping methods | Free stop, soft stop, braking stop |
| Overload capacity | 500% for 30s; 120% for long-term |
| Communication function | Standard RS485 interface |
| Protection rating | IP4X, customization available for special requirements |
| Overall structure | Cabinet type |
| Dimensions | See selection parameters for details |
| Protection functions | Phase loss protection, overheating protection |
| Operating environment | Altitude not exceeding 1000 meters; use under reduced conditions if exceeded; Ambient temperature -25°C to +45°C; maximum relative humidity 95% non-condensing; Installation location should be free of corrosive gases, conductive dust, severe vibration (less than 0.5G), and well-ventilated. |
5. Selection Reference
| Product model | Applicable motor voltage (kV) | Applicable motor power (kW) | Dimensions W*D*H (mm) |
| TCQY-1000/6 | 6 | 1000 | 1200*1660*2300 |
| TCQY-2000/6 | 6 | 2000 | 1200*1860*2300 |
| TCQY-3000/6 | 6 | 3000 | 1200*1860*2300 |
| TCQY-1000/10 | 10 | 1000 | 1200*1660*2300 |
| TCQY-2000/10 | 10 | 2000 | 1200*1860*2300 |
| TCQY-3000/10 | 10 | 3000 | 1200*1860*2300 |
6. Primary Scheme Diagram

Key words:
TCQY Series Medium and High Voltage Switchgear Magnetron Soft Sta
Leave us a message - to provide you with high-quality solutions
Committed to providing intelligent solutions for large and medium-sized motors