TBP Series Low Voltage Frequency Conversion Control Cabinet
Classification:
1. Overview
The TBP Series Low Voltage Frequency Conversion Control Cabinet is designed for three-phase asynchronous or synchronous speed regulation. It is a kind of speed control product which can change the speed of the motor by changing the supply frequency of the motor stator circuit. It is widely used in energy saving and speed control of fans and pumps in chemical industry, metallurgy, iron and steel, coal, cement and other industries.
2. Performance Features
◆ Large adjustment range, speed regulation ratio up to 20:1, high speed regulation accuracy;
◆ Energy saving effect is remarkable, the power saving rate is more than 30%, especially for variable load motors such as centrifugal fans and axial fans;
◆ With overload, lack of phase, undervoltage, three-phase unbalanced tripping and other protection functions to protect the safe operation of the motor;
◆ With serial communication interface, variable-frequency drive can be connected to remote control system.
3. Performance Parameter Table
| Item | Project Introduction | |
| Input | Rated voltage; frequency | Three-phase, 380V~440V;50Hz/60Hz |
| Single-phase, 200V~220V;50Hz/60Hz | ||
| Allowable voltage operating range | Voltage: 380V( - 15%)~ 440V(+10%),200V( - 10%)~ 220V (+10%); Voltage unbalance rate: < 3%; Frequency: ±5% | |
| Output | Voltage | 0 ~ Input voltage |
| Frequency | 0Hz ~ 550Hz | |
| Main control performance | Control method | V/F mode, vector mode |
| Speed range | 1:100(vector) | |
| Starting torque | 150% rated load at 0.50Hz | |
| Frequency accuracy | Digital setting: maximum frequency ×±0.01%; Simulation setting: maximum frequency ×±0.2% | |
| Frequency resolution | Digital setting: 0.01Hz; Simulation setting: maximum frequency x 0.1% | |
| Torque boost | Automatic torque increase, manual torque increase 0.1% ~ 30.0% | |
| V/F curve | Four modes: 1 user set V/F curve mode and 3 torque reduction characteristic curve modes (2.0 power, 1.7 power, 1.2 power) | |
| Acceleration and deceleration curve | Acceleration and deceleration time, time unit (min/sec) Optional, maximum 600 minutes | |
| Built-in PI | The closed-loop control system can be constructed conveniently | |
| Automatic energy-saving operation | According to the load, the V/F curve is automatically optimized for energy saving operation | |
| Automatic Voltage Regulation (AVR) | When the grid voltage changes, it can automatically keep the output voltage constant | |
| Protection functions | Input phase loss protection (optional), output phase loss protection (optional), overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, overload protection, etc | |
4. Selection Reference
| Model | Applicable motor power kW | Dimensions W*D*H (mm) | Mounting dimension W*D*Φ(mm) |
Cooling method |
| TBP-30/440 | ≤30 | 800*800*2000 | 750*750*14 | Air cooling |
| TBP-75/440 | 30~75 | 800*800*2000 | 750*750*14 | |
| TBP-160/440 | 75~160 | 1000*800*2000 | 850*750*14 | |
| TBP-245/440 | 160~245 | 1000*800*2000 | 850*750*14 | |
| TBP-475/440 | 245~475 | 1000*1000*2000 | 850*850*14 |
5. Primary Scheme Diagram

6. Instructions for Ordering
◆ When ordering, please provide the product model, specifications and load conditions;
◆ Ambient temperature: -40~60℃;
◆ The relative humidity of the air does not exceed 90%;
◆ The altitude does not exceed 1000 meters;
◆ Installation location: indoor, no dust, no corrosive gas, no direct sunlight;
◆ If there are particular requirements, it will be designed separately.